Data Centre Design and Construction Guide – Technical Specifications

Tier Classifications

Tier Level Uptime (%) Redundancy Power Density (kW/rack)
Tier I 99.671 N 4-8
Tier II 99.741 N+1 8-12
Tier III 99.982 2N 12-20
Tier IV 99.995 2(N+1) 20+

Power Systems

Power Distribution

Component Redundancy Capacity Monitoring
UPS 2N/2(N+1) 120% design Real-time
PDU 2N 80% rated Per rack
Generators N+1/2N 125% load Continuous
Switchgear 2N 150% rated SCADA
Transformers 2N 100% rated Temperature

Power Requirements

Area Density (kW/m²) Redundancy Backup Time
Server Hall 1.5-3.0 2N 72 hours
Network Room 1.0-1.5 2N 72 hours
Support Areas 0.2-0.4 N+1 24 hours
Offices 0.1-0.2 N 4 hours

Cooling Systems

HVAC Specifications

Parameter Requirement Standard Monitoring
Temperature 18-27°C ASHRAE TC 9.9 Continuous
Humidity 40-60% RH ASHRAE TC 9.9 Real-time
Air Flow Hot/Cold aisle EN 50600 CFD verified
PUE Target <1.3 ISO/IEC 30134 Real-time

Cooling Methods

Type Capacity (kW/rack) Efficiency (PUE) Application
CRAH 8-15 1.4-1.6 Traditional
In-Row 15-30 1.2-1.4 High density
Direct Liquid 30-50 1.1-1.3 Ultra high density
Free Cooling Variable 1.1-1.2 Climate dependent

Physical Infrastructure

Floor Loading

Area Load (kN/m²) Point Load (kN) Safety Factor
Server Floor 12-15 4.5 1.5
Battery Rooms 15-20 6.0 2.0
Equipment Rooms 10-12 3.5 1.5
Loading Areas 20-25 7.0 2.0

Raised Floor Systems

Parameter Specification Standard Testing
Height 600-1200mm EN 12825 Load tested
Panel Rating Class 5/6 MOB PF2 PS Deflection
Pedestal Rating 22kN CISCA Stability
Fire Rating 60 minutes EN 13501 Fire tested

Security Systems

Access Control

Zone Security Level Authentication Monitoring
Perimeter Level 5 Biometric+Card 24/7 CCTV
Data Hall Level 4 Biometric Man-trap
Support Areas Level 3 Card+PIN Access logs
Loading Bay Level 4 Card+CCTV Supervised

CCTV Coverage

Area Camera Type Storage Analytics
External PTZ + Fixed 90 days AI enabled
Internal 360° + Fixed 60 days Motion detect
Critical Areas Thermal 90 days Advanced
Access Points HD + Analytics 90 days Facial recognition

Fire Protection

Detection Systems

Type Coverage Response Time Standard
VESDA All areas <60 seconds EN 54-20
Smoke Double knock <90 seconds EN 54-7
Heat Critical areas <120 seconds EN 54-5
Gas Below floor <30 seconds EN 54-20

Suppression

System Application Agent Response
Gas Server halls NOVEC 1230 <10 seconds
Pre-action General areas Water Double knock
FM200 Electrical Gas <10 seconds
Water Mist Support areas High pressure Zoned

Cost Estimates (USD)

Construction Costs

Component Per m² Per MW Life Cycle
Shell 3,000-4,000 N/A 25 years
MEP 10,000-15,000 8-12M 15 years
Security 500-1,000 N/A 10 years
IT Infrastructure 2,000-3,000 1-2M 5 years

Operating Costs

Item Per kW/month Per rack/month Annual %
Power 150-200 800-1,200 45-55
Cooling 50-75 300-500 25-30
Maintenance 25-40 150-250 10-15
Security 15-25 100-150 5-10